Skip to content

4–20 mA Loop Transmitter

Calculate 4-20 mA current loop voltage budget, sensor value from loop current, and maximum loop resistance for industrial transmitter design.

Linear 4–20 mA scaling · 12 V transmitter compliance at 20 mAAPI slug 4-20ma-transmitter

Sign in to saveSave

Loop voltage budget

Supply around the loop at the loop current
Example
1 · Sense resistor21 VVsTx
Move upElementResistanceΩΣ RΩΣ DropVV at transmitterVShare of dropElement actions
Sense resistor250321100.0 %

Σ columns give each value at the row’s output: the chain cut after that row.

12 V or more

4 to 20 mA

−100 000 or more

−100 000 or more

Sensor Value
50eng units
Transmitter Voltage
21V
Voltage at Load
3V
Total Loop Resistance
250Ω
Max Loop Resistance
600Ω

Formula

I=4+16×(X−Xmin)/(Xmax−Xmin)mAI = 4 + 16 × (X − X_{min})/(X_{max} − X_{min}) mA
SymbolQuantityYour value
ILoop current (mA)—
XProcess variable (eng units)50 eng units

Assumptions

5 items
  1. 01The loop is one series circuit: the sense resistor and up to six further elements (the cable pair, an intrinsic-safety barrier, a loop-powered indicator, a HART resistor) add as resistances, R_total = R_loop + ΣR_n, and the same current flows through all of them.
  2. 02The voltage budget is Ohm’s law at the loop current entered: the drop is I_loop·R_total and the transmitter gets the supply less that drop; a barrier or an indicator is modelled as a resistance, not as a fixed voltage drop.
  3. 03The maximum loop resistance assumes the full-scale 20 mA and a 12 V minimum at the transmitter, (V_s − 12 V)/0.020 A, whatever the loop current entered and the transmitter’s own lift-off voltage, and is 0 at a 12 V supply; so below full scale the transmitter voltage is computed at the current entered, while the maximum resistance stays the 20 mA figure a design must meet.
  4. 04The reading maps the current linearly onto the range, X = X_min + (X_max − X_min)·(I − 4)/16; only 4 to 20 mA is accepted, so fault and saturation currents outside it are not interpreted.
  5. 05Cable resistance is entered as a value, not computed from the wire gauge and length, and the supply’s tolerance and ripple are not modelled.

Worked example

Transmitter at full scale through a zener barrier

A two-wire pressure transmitter, 0 to 10 bar, sits on a 24 V loop with a 250 Ω sense resistor, a 300 Ω zener barrier and 35 Ω of cable. At full scale, 20 mA, how much voltage is left at the transmitter, and is the loop within its maximum resistance?

StepExpressionResult
Total loop resistance250 + 300 + 35585 Ω
Drop around the loop at 20 mA0.02 A × 585 Ω11.7 V
Voltage left at the transmitter24 − 11.712.3 V
Maximum loop resistance(24 − 12) / 0.02 A600 Ω
Reading at 20 mA0 + (10 − 0) × (20 − 4) / 1610 eng units

How it works

This calculator designs 4-20 mA current loop transmitter and receiver circuits, essential for process control engineers, industrial automation integrators, and instrumentation technicians. The 4-20 mA current loop is the dominant standard for analog sensor transmission in industrial environments per ISA-50.00.01 and IEC 60381-1. A transmitter converts a process variable (pressure, temperature, flow, level) to proportional current: I = 4 + 16 * (X - Xmin)/(Xmax - Xmin) mA. The live zero (4 mA at zero input, not 0 mA) enables broken-wire detection (0-1 mA = fault) and powers 2-wire transmitters. Current is constant throughout the series loop, immune to voltage drops over cable runs up to 3000 m with 24V supply. The receiver converts current to voltage across a burden resistor (typically 250 Ohm for 1-5V output). Maximum loop resistance = (Vsupply - Vtx_min) / 20 mA; with 24V supply and 12V minimum transmitter voltage, R_max = 600 Ohm. HART protocol superimposes +/-0.5 mA FSK at 1200 bps for digital communication without disturbing the analog signal.

Practical tips

  • Use 18-24 AWG twisted-pair cable with overall shield for 4-20 mA runs; ground the shield at the control room end only to avoid ground-loop currents per ISA-RP12.06.01 installation practices
  • Add transient protection (TVS diode or gas discharge tube) at both ends of long cable runs; lightning-induced surges can exceed 1000V and damage transmitters and PLC inputs per IEC 61643-21
  • For HART-enabled transmitters, ensure minimum 230 Ohm load for communication; if burden is <230 Ohm, add external 250 Ohm resistor in parallel with HART modem per HART Foundation specification

Common mistakes

  • Connecting multiple receivers in series without summing burden resistances: two 250 Ohm inputs in series = 500 Ohm burden, halving maximum cable resistance allowance; verify total loop resistance stays below (Vsupply - Vtx_min)/20 mA
  • Interpreting 4 mA as 'fault' instead of 'zero': 4 mA represents zero process input per ISA-50.00.01; fault condition is <3.6 mA (NAMUR NE43 defines 3.6-3.8 mA as under-range, <3.6 mA as sensor failure)
  • Measuring 4-20 mA with voltmeter across open loop: inserting a high-impedance voltmeter breaks the current path; measure voltage across known burden resistor (V = I * R_burden) or use clamp-on mA meter

Frequently asked questions

3 questions
Why is the live zero 4 mA instead of 0 mA?

The 4 mA live zero serves three critical functions per ISA-50.00.01: (1) powers 2-wire transmitters - the transmitter operates on the loop current it regulates, requiring minimum 3.5-4 mA to function, (2) enables broken-wire detection - a reading of 0-3.6 mA indicates open circuit or failed transmitter versus genuine zero process value, (3) allows transmitters on single 24V supply without separate power wiring. NAMUR NE43 defines: <3.6 mA = sensor failure, 3.6-3.8 mA = under-range, 20.5-21 mA = over-range, >21 mA = output saturated.

What is the maximum cable length for a 4-20 mA loop?

Maximum length depends on cable resistance and transmitter voltage requirement. With 24V supply, 250 Ohm burden, 12V minimum transmitter voltage: R_cable_max = (24 - 12 - 250*0.020)/0.020 = 350 Ohm. For 18 AWG (20.9 Ohm/km), max length = 350/20.9/2 = 8.4 km one-way (16.7 km of conductor). Practical limit with margin for connectors and temperature variation is typically 2-3 km. For longer runs, use 4-20 mA to digital converters (HART, Modbus) at the field end per ISA-50.00.01.

How does HART coexist with the 4-20 mA signal?

HART (Highway Addressable Remote Transducer) modulates a +/-0.5 mA peak FSK signal onto the DC current using Bell 202 frequencies (1200 Hz = '1', 2200 Hz = '0') at 1200 bps. The AC component averages to zero over each bit, so it does not affect the 4-20 mA process reading. The burden resistor (minimum 230 Ohm per HART spec) converts current modulation to voltage that a HART modem can detect. HART enables remote configuration, diagnostics, and secondary variables while maintaining backward compatibility with analog-only receivers.