Skip to content

Pressure Sensor Bridge Output

Calculate bridge output voltage for piezoresistive pressure sensors. Determine mV output from excitation voltage, sensitivity, and applied pressure.

Linear ratiometric bridge · V = V_ex·S·P/P_FSAPI slug pressure-bridge-output

Sign in to saveSave

Sensor and circuit

Example
Sensor
Full-scale output in mV per V of excitation
mV/V

0.001 mV/V or more

kPa

0.001 kPa or more

Circuit

100 mV or more

The gain between the bridge output and the ADC. A gain of 60 brings a 50 mV full-scale output to 3 V.
V/V

0.01 to 100 000 V/V

The ADC full scale

100 mV to 50 V

ADC resolution in bits
bit

1 to 24 bit

P×60ADC3.3 V

Convert

kPa

0 kPa to 100 000 kPa

Bridge Output
25mV
Amplifier Output
1.5V
ADC Code
1 861
0x745
Full-Scale Output
50mV
Fractional Deflection
50.0%
Resolution
0.02686kPa/LSB

Transfer curves

Resolution 0.02686 kPa/LSB across the range
0 mV10 mV20 mV30 mV40 mV50 mV020406080100 kPaBridge Output
05001 0001 5002 0002 5003 0003 500020406080100 kPaADC Code

Lookup table

Every 5 kPa from 0 kPa to 100 kPa
CSV (sign in)
Applied PressureBridge OutputAmplifier OutputADC Code
0kPa0mV0V0
5kPa2.5mV150mV186
10kPa5mV300mV372
15kPa7.5mV450mV558
20kPa10mV600mV744
25kPa12.5mV750mV930
30kPa15mV900mV1 117
35kPa17.5mV1.05V1 303
40kPa20mV1.2V1 489
45kPa22.5mV1.35V1 675
50kPa25mV1.5V1 861
55kPa27.5mV1.65V2 048
60kPa30mV1.8V2 234
65kPa32.5mV1.95V2 420
70kPa35mV2.1V2 606
75kPa37.5mV2.25V2 792
80kPa40mV2.4V2 978
85kPa42.5mV2.55V3 165
90kPa45mV2.7V3 351
95kPa47.5mV2.85V3 537
100kPa50mV3V3 723

Formula

Vout=Vex×S×(P/PFS)V_{out} = V_{ex} × S × (P/P_{FS})
SymbolQuantityYour value
SSensitivity (mV/V)10 mV/V
PFSFull-scale pressure (kPa)100 kPa

Assumptions

6 items
  1. 01The sensor is linear and ratiometric, V_out = V_ex × S × P/P_FS, with S the full-scale output per volt of excitation; zero offset, span tolerance, non-linearity, hysteresis and temperature effects are not modelled.
  2. 02Pressure is in the unit of the full-scale pressure, kPa on the page, and is not limited to full scale, so a pressure above P_FS reads more than 100 % deflection.
  3. 03The excitation is an ideal source, and the amplifier an ideal gain G with no offset, noise or bandwidth limit that does not load the bridge.
  4. 04The ADC is an ideal unipolar N-bit converter with full scale V_ref and no INL, DNL or noise: code = floor(V_amp/V_ref × 2^N), held between 0 and 2^N − 1, so an output below zero reads 0 and one at or above V_ref reads 2^N − 1.
  5. 05A code typed in is read at the middle of its step, (code + 0.5)/2^N × V_ref, and solved back through the same model.
  6. 06Resolution is V_ref × P_FS/(2^N × G × V_ex × S × 10⁻³) per step with S in mV/V, the same at every pressure because the model is linear.

Worked example

100 kPa sensor at 60 kPa

An MPX2100-class 100 kPa piezoresistive sensor gives 4 mV/V at full scale. Excited at 5 V and read through a gain-150 amplifier into a 3.3 V, 12-bit ADC, it sees 60 kPa.

StepExpressionResult
Full-scale output4 mV/V × 5 V20 mV
Fraction of full scale60 kPa / 100 kPa60.0 %
Bridge output20 mV × 60.0 %12 mV
Amplifier output150 × 12 mV1.8 V
ADC codefloor(1.8 / 3.3 × 2^12)2 234
Resolution3.3 V × 100 kPa / (2^12 × 150 × 20 mV)0.02686 kPa/LSB

How it works

This calculator computes piezoresistive pressure sensor bridge output voltage, essential for process control engineers, HVAC system designers, and automotive sensor integrators. Piezoresistive pressure sensors contain a Wheatstone bridge of diffused or thin-film strain gauges on a silicon or steel diaphragm. Applied pressure deflects the diaphragm, changing resistance to unbalance the bridge. Output is Vout = Vex * S * (P/Pfs), where Vex is excitation voltage (5-10V typical), S is sensitivity in mV/V (typically 10-30 mV/V per OIML recommendations), P is applied pressure, and Pfs is full-scale pressure. A 20 mV/V sensor on 5V excitation produces 100 mV at full scale. Per IEC 61298, pressure sensor specifications include accuracy (+/-0.1 to +/-1% FS), nonlinearity (+/-0.1-0.5% FS), hysteresis (+/-0.05-0.2% FS), and thermal zero shift (typically +/-0.02% FS/C). Industrial sensors from Honeywell, Sensata, and Bosch achieve total error band (TEB) of +/-0.25% FS over -40 to +125C per AEC-Q100 automotive qualification.

Practical tips

  • Use ratiometric operation: connect both ADC reference and sensor excitation to the same regulated voltage; if supply fluctuates +/-5%, both scale proportionally and ratio Vout/Vex remains constant per Honeywell Technical Note HSC-AN-800
  • For absolute accuracy, perform two-point calibration at zero pressure and known reference pressure (NIST-traceable calibrator) to correct for both offset and gain errors per ISO 17025 requirements
  • Add 100 nF ceramic capacitors from each excitation line to ground, close to the sensor, to filter high-frequency noise from PWM switching that would appear as measurement noise

Common mistakes

  • Applying excitation exceeding sensor maximum: overvoltage causes bridge self-heating, shifting zero by 0.1-1% FS and degrading accuracy; verify maximum excitation (typically 5-12V) per manufacturer datasheet
  • Installing sensor upside-down relative to calibrated orientation: many sensors include diaphragm dead-weight in zero calibration; orientation change causes offset shift equal to diaphragm pressure head (0.1-1% FS for liquid-filled sensors)
  • Neglecting common-mode voltage at amplifier input: bridge output rides on Vex/2 common mode; choose INA with input range including Vex/2 on your supply rails per Texas Instruments INA128 datasheet

Frequently asked questions

3 questions
What is the difference between gauge, absolute, and differential pressure sensors?

Gauge sensors measure relative to atmospheric pressure (zero output at 1 atm); used for tire pressure, tank level, HVAC. Absolute sensors measure relative to vacuum (zero output at 0 Pa); used for altimeters, barometers, MAP sensors. Differential sensors measure pressure difference between two ports (positive for P1>P2, negative for P1

What is thermal zero offset and how is it compensated?

Thermal zero offset is shift in bridge output at zero pressure caused by temperature-induced resistance imbalance. Specified as +/-0.02% FS/C typical per IEC 61298. Over 100C range, this is 2% FS error. Compensation methods: (1) analog using thermistor in bridge network, (2) digital using on-chip temperature sensor plus polynomial correction (integrated sensors like Honeywell HSC, Bosch BMP390). Digital sensors achieve +/-0.5% TEB over full temperature range versus +/-2% for uncompensated analog sensors.

How do I select bridge excitation voltage?

Higher excitation gives larger output (better SNR) but increases self-heating. Self-heating error = (Vex^2/Rbridge) * thermal_resistance. For 350 Ohm bridge at 10V: P = 100/350 = 286 mW. With 0.1 C/mW thermal resistance, self-heating is 28.6 C, causing 0.6% FS error at 0.02%/C drift. Standard practice: use 5V for silicon bridges rated 5-10V maximum. For battery-powered applications, use minimum recommended voltage (often 3V) to reduce power to <26 mW per Honeywell HSC low-power modes.