Skip to content

Cable Voltage Drop Calculator

Calculate voltage drop across a cable run. Enter supply voltage, load current, wire gauge (AWG), and one-way distance to get voltage drop in volts and percent, power loss, and NEC 3%/5% compliance status. Supports copper and aluminum conductors.

AWG resistance at 20 °C, round-trip I·R · NEC 3 %/5 % guidanceAPI slug voltage-drop

Sign in to saveSave

1 V to 10 kV

100 mA to 1 kA

Distance from panel to load (not round-trip)

500 mm to 5 km

Wire sizes

Select wireWireConductorDropDrop%Power lostCompare
1/0 AWGCopper290.2mV0.244.352W
2 AWGCopper461.4mV0.46.921W
4 AWGCopper733.7mV0.611.01W
6 AWGCopper1.166V1.017.5W
8 AWGCopper1.855V1.527.82W
10 AWGCopper2.949V2.544.24W
12 AWGCopper4.69V3.970.35W
14 AWGCopper7.457V6.2111.9W
16 AWGCopper11.85V9.9177.8W
18 AWGCopper18.85V15.7282.8W
20 AWGCopper29.98V25.0449.7W
22 AWGCopper47.66V39.7715W
24 AWGCopper75.8V63.21.137kW
1/0 AWG aluminiumAluminium475.7mV0.47.135W
2 AWG aluminiumAluminium756.4mV0.611.35W
4 AWG aluminiumAluminium1.203V1.018.04W
6 AWG aluminiumAluminium1.912V1.628.68W
8 AWG aluminiumAluminium3.041V2.545.61W
10 AWG aluminiumAluminium4.835V4.072.52W
12 AWG aluminiumAluminium7.688V6.4115.3W
14 AWG aluminiumAluminium12.23V10.2183.4W
16 AWG aluminiumAluminium19.43V16.2291.5W
18 AWG aluminiumAluminium30.91V25.8463.6W
20 AWG aluminiumAluminium49.14V41.0737.2W
22 AWG aluminiumAluminium78.14V65.11.172kW
24 AWG aluminiumAluminium124.3V103.51.864kW
Copper at 20 °C, IEC 60028 (1/58 Ω·mm²/m), over each size’s ASTM B258 area; aluminium IEC 60889 (0.028264 Ω·mm²/m); round-trip run26 of 26 shownCSV (sign in)

12 AWG · Voltage Drop

4.69V
vs 10 AWG
+1.74V
Voltage Drop
3.9%
Voltage at Load
115.3V
Max Length for 3% Drop
23.03m

Voltage Drop against One-Way Distance

4 compared
16 AWG14 AWG12 AWG10 AWG01020304050607050 m100 m150 m200 m%
Round-Trip ResistanceRtotal
313mΩ
NEC Status (1=OK, 2=Marginal, 3=Fail)
2

Formula

Vdrop=I⋅2⋅d⋅R/km1000V_{drop} = I \cdot \frac{2 \cdot d \cdot R_{/km}}{1000}
SymbolQuantityYour value
ILoad current (A)15 A
dOne-way cable length (m)30 m
RkmWire resistance per km (from AWG) (Ω/km)—
Vdrop%Drop as percentage of supply (%)—

Assumptions

6 items
  1. 01DC or single-phase: the current flows out and back, so the resistance is 2·d·R_km/1000 with d the one-way distance, and the drop is I × R_total; three-phase (√3·I·R) is not offered.
  2. 02R_km is copper's resistance at 20 °C, IEC 60028's 1/58 Ω·mm²/m over the gauge's ASTM B258 area: a table for the even gauges 1/0 to 24 AWG, the steps the input takes (12 AWG 5.211 Ω/km), and the same formula for any other gauge; the conductor's temperature rise at load is not applied.
  3. 03Aluminium is taken as 1.639 times copper's resistance for the same gauge: IEC 60889's 0.028264 Ω·mm²/m over copper's 1/58 (61 % IACS).
  4. 04Resistance only, at the current entered: the cable's reactance, which matters for large conductors on AC, and any change of the load's current with the voltage at it are not modelled.
  5. 05The power lost is I²·R_total, and the status compares the percentage drop with the NEC's informational guidance of 3 % for a branch and 5 % for feeder and branch: 1 up to 3 %, 2 up to 5 %, 3 above.
  6. 06The maximum length is the one-way distance at which the drop reaches 3 %, 0.03·V·1000/(2·I·R_km).

Worked example

A 15 A branch 30 m out: 12 or 10 AWG

A 120 V branch circuit feeds a 15 A load 30 m from the panel. Does 12 AWG copper, the size usual for a 20 A circuit, keep the drop within the NEC's 3 % guidance, or does the run need 10 AWG?

StepExpressionResult
12 AWG first15 A × 2 × 30 m × 5.211 Ω/km4.69 V
12 AWG as a share of 120 V: over 3 %, marginal4.69 / 120 × 1003.91 %
Round-trip resistance, 10 AWG2 × 30 m × 3.277 Ω/km197 mΩ
Voltage drop15 A × 197 mΩ2.949 V
As a share of 120 V2.949 / 120 × 1002.5 %
Longest run within 3 %3 % × 120 V / (2 × 15 A × 3.277 Ω/km)36.62 m
10 AWG aluminium instead15 A × 2 × 30 m × 3.277 Ω/km × 1.6394.83 V
Aluminium as a share of 120 V4.83 / 120 × 1004.03 %
Aluminium needs 8 AWG15 A × 2 × 30 m × 2.061 Ω/km × 1.639 / 120 V2.53 %

How it works

Voltage drop across a cable is the reduction in voltage between the source (panel/PSU) and the load, caused by conductor resistance. Per Ohm's law, V_drop = I x R_total, where R_total is the round-trip resistance (outgoing + return conductor). For single-phase or DC circuits, the total cable resistance is 2 x length x R_per_km / 1000, doubling the one-way distance because current flows through both conductors. The NEC (National Electrical Code, Article 210.19 Informational Note 4) recommends maximum 3% voltage drop for branch circuits and 5% total (feeder + branch) for acceptable performance. These are recommendations, not requirements, but exceeding them causes reduced equipment performance, increased heating, motor torque reduction, and LED/lighting flicker. Wire resistance depends on material (copper: 1.72e-8 ohm-m, aluminum: 2.82e-8 ohm-m at 20C), cross-sectional area, and temperature. AWG (American Wire Gauge) is logarithmic: each 3-gauge increase doubles the resistance (halves the area). Temperature increases resistance by approximately 0.393%/C for copper above 20C. For long cable runs (solar arrays, EV charging, large motors), voltage drop often requires oversizing conductors beyond the minimum ampacity rating from NEC Table 310.16.

Practical tips

  • Quick reference for 120V copper circuits at maximum 3% drop (3.6V): 14 AWG = 15A max 14m, 12 AWG = 20A max 17m, 10 AWG = 30A max 18m. For 240V circuits (7.2V drop budget), distances double. For 12V DC systems, distances are 1/10th of 120V values — this is why low-voltage solar and automotive systems require very thick cables for any meaningful distance.
  • Aluminum conductors have about 1.64x the resistance of copper for the same gauge. To get equivalent performance, upsize aluminum by 2 AWG (e.g., use 2 AWG aluminum where you'd use 4 AWG copper). Aluminum is common in service entrance cables (SE, SER) and large feeders because it's lighter and cheaper, despite needing larger conduit. Always use aluminum-rated terminals (AL/CU marked) to prevent galvanic corrosion.
  • For solar installations, voltage drop is especially critical because you lose energy at both low voltage AND high current conditions. A 3% drop at rated current means 3% of generated energy is lost as heat in cables every day. Over 25 years, this adds up to significant lifetime energy loss. Many solar designers target 1-2% drop, accepting the higher upfront wire cost for better lifetime ROI. Use the 'max length for 3%' output to verify your cable sizing.
  • Parallel conductors reduce effective resistance. Two identical cables in parallel halve the resistance (and the voltage drop). NEC 310.10(H) allows paralleling conductors 1/0 AWG and larger. For large loads where a single cable would be impractically thick (e.g., 200A at 100m), using two parallel runs of smaller cable is often more practical and may be cheaper than a single oversized cable. Each parallel conductor must have identical length, material, and termination.

Common mistakes

  • Forgetting to account for the return conductor (doubling the distance). In a DC or single-phase AC circuit, current flows through BOTH conductors (hot and neutral/return). The total resistance is 2x the one-way cable resistance. This is the most common error and results in actual voltage drop being double the calculated value. Only three-phase balanced loads use a factor of sqrt(3) instead of 2.
  • Using NEC Table 310.16 ampacity ratings to size cables for long runs. Table 310.16 gives the MAXIMUM current a conductor can carry without overheating (thermal limit), but it does NOT account for voltage drop. A 12 AWG wire is rated 20A for ampacity, but over a 50m run at 20A on 120V, the drop is 8.7% (far exceeding 3%). Always check voltage drop separately from ampacity; for long runs, voltage drop usually requires oversizing the conductor.
  • Ignoring temperature effects on resistance. Copper resistance increases ~0.393%/C above 20C. In a hot attic (60C), resistance increases by 15.7%. In a solar installation where cables reach 75C under sun exposure, resistance increases by 21.6%. NEC Table 8 values are at 75C (not 20C) precisely for this reason. For critical calculations (large solar arrays, data centers), use resistance values at expected operating temperature.
  • Applying single-phase voltage drop formulas to three-phase systems. For balanced three-phase loads, V_drop = sqrt(3) x I x R x L / 1000 (line-to-line drop), or equivalently, the multiplier is 1.732 instead of 2. Using the single-phase formula (multiplier = 2) overestimates three-phase drop by 15%. Also note: for three-phase, the 'length' is still one-way distance since current returns through the other two phases.

Frequently asked questions

4 questions
What is acceptable voltage drop per NEC?

NEC recommends (not requires) maximum 3% voltage drop for branch circuits and 5% total for feeder + branch combined (Article 210.19 Informational Note 4 and 215.2 Informational Note 2). For 120V: 3% = 3.6V drop, 5% = 6V drop. For 240V: 3% = 7.2V, 5% = 12V. For 12V DC (solar/automotive): 3% = 0.36V. Note these are informational notes, not mandatory requirements. However, many local jurisdictions and project specifications enforce them. Sensitive equipment (VFDs, PLCs, medical devices) may require tighter limits of 1-2%.

How do I reduce voltage drop?

Five approaches: (1) Increase wire gauge (most common) — each 3-AWG increase halves resistance; (2) Shorten cable run — relocate panel or equipment closer; (3) Increase system voltage — 240V has 1/4 the drop of 120V for same power delivery; (4) Use parallel conductors — two cables halve the drop; (5) Reduce current — use higher voltage or lower power equipment. For existing installations where rewiring is impractical, options 3-5 may be more cost-effective than pulling new cable.

Does voltage drop matter for AC circuits?

Yes, equally as DC for resistive loads. For AC circuits, impedance (not just resistance) matters: Z = sqrt(R^2 + X_L^2), where X_L is inductive reactance of the cable. For small conductors (14-10 AWG) at 60 Hz, reactance is negligible. For large conductors (4/0+) in steel conduit, inductive reactance can add 20-30% to effective impedance. This calculator uses resistance only, which is accurate for residential/light commercial wiring (14-6 AWG). For large industrial feeders (500 kcmil in conduit), use NEC Chapter 9 Table 9 which includes reactance.

Why is voltage drop worse for 12V systems than 120V?

For the same power delivery, a 12V system carries 10x the current of a 120V system (P=V*I). Since voltage drop is V_drop = I*R, the 10x higher current creates 10x the voltage drop in the same cable. Additionally, the 3% budget is only 0.36V at 12V vs 3.6V at 120V. Combined effect: a 12V system needs approximately 100x lower resistance (much thicker, shorter cables) to deliver the same power within the same percentage drop limit. This is why solar arrays, data centers, and EV charging use higher voltages (48V, 380VDC, or 400VAC) for efficiency.

Shop Components

As an Amazon Associate we earn from qualifying purchases.

  • DC-DC Buck Converter ModulesAdjustable step-down converter modules for bench and prototype useAmazon →
  • LDO Voltage Regulator KitAssorted low-dropout linear regulators for prototypingAmazon →
  • Electrolytic Capacitor KitAluminum electrolytic capacitor kit for power supply filteringAmazon →
  • Power Inductor KitAssorted shielded power inductors for switching supply designsAmazon →