RS-485 Termination & Bias Resistor Calculator

POSThttps://rftools.io/api/py/v1/calculate

Slug rs485-termination. Calculate RS-485 bus termination resistors, bias resistors, maximum baud rate for cable length, propagation delay, and bias current consumption

Inputs

Send every one of these in inputs, in the units shown. Most are required: a call without one is refused (400) and costs nothing; one the calculator can do without takes the default shown. An input outside its range is still computed and flagged in the provenance.

Inputs of rs485-termination
NameUnitRangeDefaultDescription
baudRatenumberkbpsat least 0.1115.2RS-485 communication baud rate in kbps
cableLengthnumbermat least 0.1100Total bus cable length in meters
supplyVoltagenumberV3 … 5.55Logic supply voltage for the RS-485 transceivers
eSeriesnumbernone0 … 960Rounds every part to the nearest value in the series; the response and the export are the rounded design's.One of: 0 Ideal values · 12 E12 (10%) · 24 E24 (5%) · 48 E48 (2%) · 96 E96 (1%)

Retired, still accepted and ignored with a warning: numNodes (Number of Nodes, 2026-10-12).

Outputs

Returned in values, by key. A value that is unbounded or undefined is null.

Outputs of rs485-termination
FieldUnitDescription
terminationResistorheadlineΩMatch to cable characteristic impedance (~120Ω for twisted pair); 121 Ω in E48 and E96
biasResistorΩFailsafe bias resistors to maintain idle state differential voltage > 200 mV; rounded to the part series when one is chosen
maxBaudRatekbpsMax Baud Rate for Cable Length
propagationDelaynsCable Propagation Delay
loadCurrentmABias Load Current
baudRateUtilisation%The entered baud rate as a share of the maximum for this cable length (rate × length ≤ 10⁸ bit·m); above 100 % the cable is too long for the rate
failsafeVoltagemVThe A–B voltage the bias resistors hold on the idle bus across the two terminators in parallel, Vcc·(R_term/2)/(2·R_bias + R_term/2); TIA-485-A receivers need at least 200 mV to read it as a defined state (TI SLLA272C)