Skip to content

Wire Gauge Calculator (AWG)

Convert between AWG and mm², calculate wire current capacity, resistance, and voltage drop

ASTM B258 AWG diameter · R = ρL/A · 2.5 A/mm² ruleAPI slug wire-gauge

Sign in to saveSave

0 A or more

0 m or more

Copper = 0.01724, Aluminum = 0.0282
Ω·mm²/m

Wire sizes

Select wireWireDiameterAreamm²Voltage dropCurrent capacityCompare
1/0 AWG8.251mm53.48322.4µV133.7A
1 AWG7.348mm42.41406.5µV106A
2 AWG6.544mm33.63512.6µV84.08A
3 AWG5.827mm26.67646.4µV66.68A
4 AWG5.189mm21.15815.1µV52.88A
5 AWG4.621mm16.771.028mV41.93A
6 AWG4.115mm13.31.296mV33.25A
7 AWG3.665mm10.551.634mV26.37A
8 AWG3.264mm8.3662.061mV20.91A
9 AWG2.906mm6.6342.599mV16.59A
10 AWG2.588mm5.2613.277mV13.15A
11 AWG2.305mm4.1724.132mV10.43A
12 AWG2.053mm3.3095.21mV8.272A
13 AWG1.828mm2.6246.57mV6.56A
14 AWG1.628mm2.0818.285mV5.202A
15 AWG1.45mm1.6510.45mV4.126A
16 AWG1.291mm1.30913.17mV3.272A
17 AWG1.15mm1.03816.61mV2.595A
18 AWG1.024mm0.82320.95mV2.058A
19 AWG911.6µm0.652726.41mV1.632A
20 AWG811.8µm0.517633.31mV1.294A
21 AWG722.9µm0.410542mV1.026A
22 AWG643.8µm0.325552.96mV813.8mA
23 AWG573.3µm0.258266.78mV645.4mA
24 AWG510.6µm0.204784.21mV511.8mA
25 AWG454.7µm0.1624106.2mV405.9mA
26 AWG404.9µm0.1288133.9mV321.9mA
27 AWG360.6µm0.1021168.8mV255.3mA
28 AWG321.1µm0.08098212.9mV202.4mA
29 AWG285.9µm0.06422268.5mV160.5mA
30 AWG254.6µm0.05093338.5mV127.3mA
31 AWG226.8µm0.04039426.9mV101mA
32 AWG201.9µm0.03203538.3mV80.07mA
33 AWG179.8µm0.0254678.8mV63.5mA
34 AWG160.1µm0.02014855.9mV50.36mA
35 AWG142.6µm0.015971.079V39.93mA
36 AWG127µm0.012671.361V31.67mA
37 AWG113.1µm0.010051.716V25.11mA
38 AWG100.7µm0.0079672.164V19.92mA
39 AWG89.69µm0.0063182.729V15.79mA
40 AWG79.87µm0.005013.441V12.53mA
AWG diameter d = 0.127 mm × 92^((36 − AWG)/39) (ASTM B258); resistance from the resistivity entered41 of 41 shownCSV (sign in)

22 AWG · Cross-Section Area

0.3255mm²
vs 21 AWG
−0.085mm²
Wire Resistance
53mΩ
Voltage Drop
52.96mV
Current Capacity
813.8mA

Voltage Drop against Wire Length

4 compared
24 AWG23 AWG22 AWG21 AWG01234510 m20 m30 m40 m50 mV

Formula

ASTM B258 - Standard Specification for Standard Nominal Diameters
d=0.127×92((36−AWG)/39)mm,A=π(d/2)2d = 0.127 × 92^((36-\mathrm{AWG})/39) mm,\quad A = π(d/2)²
SymbolQuantityYour value
dWire diameter (mm)643.8 µm
AWGAmerican Wire Gauge number22 AWG
ACross-sectional area (mm²)0.3255 mm²
ρResistivity (Ω·mm²/m)0.01724 Ω·mm²/m
LWire length (m)1 m

Assumptions

5 items
  1. 01The diameter is ASTM B258's AWG series, d = 0.127 mm × 92^((36 − AWG)/39), for a solid round conductor, and the area is π·d²/4; gauge 0 is 1/0.
  2. 02Resistance is ρ·L/A with the resistivity and length entered (0.01724 Ω·mm²/m by default, copper at 20 °C), with no temperature coefficient, stranding or skin effect.
  3. 03The voltage drop is I × R over the length entered, one conductor: for a circuit out and back, enter the length of both conductors.
  4. 04The current capacity is a fixed current density, 2.5 A/mm² times the area, whatever the resistivity; it is not an NEC 310.16 or IEC ampacity, and insulation rating, ambient, bundling and installation are not applied.
  5. 05It reads well below the NEC table for building wire: 12 AWG gives 8.3 A, where NEC 310.16 rates 20 A in 60 °C insulation.

Worked example

Hookup wire for a 3 A load 2 m away

A 3 A load sits 2 m from its supply, so the current flows through 4 m of copper wire, out and back. Which gauge does the 2.5 A/mm² rule allow, and what does that wire drop?

StepExpressionResult
Diameter of 16 AWG0.127 mm × 92^((36 − 16)/39)1.291 mm
Cross-sectionπ × (1.291/2)²1.309 mm²
Current capacity at 2.5 A/mm²2.5 × 1.3093.272 A
Resistance of 4 m0.01724 × 4 ÷ 1.30952.7 mΩ
Voltage drop at 3 A3 × 0.0527158.1 mV
Why not 18 AWG: its diameter0.127 mm × 92^((36 − 18)/39)1.024 mm
Its current capacity, under 3 A2.5 × π × (1.024/2)²2.06 A

How it works

This calculator converts AWG (American Wire Gauge) to diameter and metric mm^2 cross-section for electrical engineers and international projects requiring wire size standardization. Per ASTM B258, AWG diameter follows d(inches) = 0.005 × 92^((36-AWG)/39), while IEC 60228 defines metric sizes in mm^2 cross-sectional area (0.5, 0.75, 1.0, 1.5, 2.5, 4, 6, 10, 16, 25, 35... mm^2). Key conversions: AWG 14 = 2.08 mm^2 (nearest IEC: 2.5 mm^2), AWG 12 = 3.31 mm^2 (nearest: 4 mm^2), AWG 10 = 5.26 mm^2 (nearest: 6 mm^2). Copper resistivity is 1.724 × 10^-8 ohm·m at 20 C per NIST; resistance R = rho × L / A. Temperature coefficient: +0.393%/C for copper, +0.403%/C for aluminum. Proper gauge selection prevents 15-25% efficiency loss from voltage drop in long runs.

Practical tips

  • AWG to IEC conversion per common practice: AWG 18 = 0.82 mm^2 (use 1.0), AWG 16 = 1.31 mm^2 (use 1.5), AWG 14 = 2.08 mm^2 (use 2.5), AWG 12 = 3.31 mm^2 (use 4.0), AWG 10 = 5.26 mm^2 (use 6.0). Always round UP to next IEC size for safety
  • Voltage drop rule of thumb: keep < 3% for branch circuits, < 5% total per NEC. At 120 V/15 A, 3% = 3.6 V max drop = 0.24 ohm round-trip. Use 2 × length × resistance-per-foot calculation
  • Aluminum requires 2 AWG upsize vs copper for equal ampacity (61% conductivity per ASTM). AWG 12 Cu = AWG 10 Al. Also requires antioxidant compound on connections per NEC 110.14

Common mistakes

  • Using wrong conversion - AWG 12 = 3.31 mm^2, NOT 12 mm^2. AWG is logarithmic; metric mm^2 is linear. Each 3 AWG steps = 2× area, so AWG 9 = 6.63 mm^2, AWG 6 = 13.3 mm^2, AWG 3 = 26.7 mm^2
  • Ignoring temperature coefficient - copper resistance increases 21.5% from 20 C to 75 C operating temperature. A 0.156 ohm wire at 20 C becomes 0.190 ohm at 75 C. Use operating temperature for voltage drop calculations
  • Confusing solid vs stranded conductor area - per ASTM B8, stranded wire has 2-3% larger OD for same cross-sectional area. AWG numbers apply to copper cross-section, not overall diameter

Frequently asked questions

5 questions
What is the difference between AWG and mm^2?

AWG is a North American logarithmic scale per ASTM B258; lower number = larger wire. mm^2 is direct cross-sectional area per IEC 60228. Conversion is non-linear: AWG 12 = 3.31 mm^2, AWG 10 = 5.26 mm^2, AWG 8 = 8.37 mm^2. IEC sizes follow a preferred number series: 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50 mm^2.

How do temperature variations affect wire performance?

Per NIST: copper resistance = R_20 × (1 + 0.00393 × (T - 20)). At 75 C: 1.22× resistance vs 20 C. At -40 C: 0.76× resistance. Ampacity tables (NEC 310.16) account for insulation temperature rating and ambient. High ambient reduces ampacity; cold environments allow higher current.

Can I use aluminum instead of copper wire?

Yes, with proper derating per NEC. Aluminum conductivity = 61% of copper (ASTM B8). Use 2 AWG sizes larger: AWG 12 Cu = AWG 10 Al for same ampacity. Require AL/CU rated terminals and antioxidant compound. Aluminum is common for > AWG 8 due to cost savings (30-50% cheaper than copper per lb).

What determines wire current capacity?

Per NEC 310.15: cross-sectional area (larger = more current), insulation temperature rating (60/75/90 C), ambient temperature, number of conductors bundled, and installation method (conduit vs free air). Ampacity = safe current without exceeding insulation temperature limit. Voltage drop may further limit practical current.

How do I prevent voltage drop in long circuits?

Per NEC 210.19 guideline (< 3% drop): upsize wire, reduce circuit length, or increase voltage. Voltage drop = I × R × 2 (for round trip). For 100 ft at 15 A with AWG 14: V_drop = 15 × 0.00252 × 200 = 7.6 V (6.3% at 120 V - too high). Upsize to AWG 12: 4.8 V (4%), or AWG 10: 3.0 V (2.5% - compliant).

Shop Components

As an Amazon Associate we earn from qualifying purchases.

  • Resistor Kit (1%, E24)Precision 1% thin-film SMD resistor assortment, 0402 packageAmazon →
  • Ceramic Capacitor KitMLCC ceramic capacitor assortment in 0402 packageAmazon →
  • Solderless BreadboardFull-size breadboard for circuit prototypingAmazon →