Steinmetz Connection Calculator — Run a Three-Phase Motor on Single Phase

POSThttps://rftools.io/api/py/v1/calculate

Slug steinmetz-connection. Size the run and start capacitors for a three-phase induction motor on a single-phase supply (the Steinmetz connection, or static phase converter), and see what the motor does with them: the three voltages, how unbalanced they are, the most loaded winding's current, the usable output and the voltage each capacitor must be rated for. A second mode gives the capacitor and inductor that balance the motor exactly.

Inputs

Send every one of these in inputs, in the units shown. Most are required: a call without one is refused (400) and costs nothing; one the calculator can do without takes the default shown. An input outside its range is still computed and flagged in the provenance.

Inputs of steinmetz-connection
NameUnitRangeDefaultDescription
supplyVoltagenumberVat least 1230The single-phase supply, which must equal the motor's rated line voltage in the connection used: a 230/400 V motor in delta on 230 V, a 208–230/460 V motor in its low-voltage connection on 240 V.
frequencynumberHzat least 150Supply Frequency
ratedCurrentnumberAat least 0.0018.3The nameplate current for the connection used (the delta current of a 230/400 V motor on 230 V).
powerFactornumbernone0.01 … 10.81The nameplate cos φ at rated load.
ratedPowernumberkWat least 0.0012.2The nameplate shaft power; it scales the usable-output estimate.
lockedRotorRationumber×at least 1.016Starting current as a multiple of rated, from the catalogue or the nameplate code letter; 5 to 7 is typical.
lockedRotorPFnumbernone0.01 … 10.4Power factor at standstill; 0.3 to 0.5 is typical of small cage motors.
noLoadCurrentnumber%1 … 9940Current running unloaded, as a percentage of rated; 30 to 60 % is typical of small motors.
noLoadPFnumbernone0.01 … 10.1Power factor running unloaded; 0.05 to 0.2 is typical.
modenumbernone0 … 10A run capacitor alone, or the exact balancer: a capacitor on L3–L1 and an inductor (or second capacitor) on L3–L2.One of: 0 Run capacitor only · 1 Balancer (capacitor + inductor)
runCapacitornumberµFat least 00The run capacitor you have, to see what it does; 0 uses the recommended one. Run-capacitor mode only.
startTorqueTargetnumber%at least 150Starting torque wanted, as a percentage of the motor's three-phase locked-rotor torque.

Outputs

Returned in values, by key. A value that is unbounded or undefined is null.

Outputs of steinmetz-connection
FieldUnitDescription
runCapacitorheadlineµFRun Capacitor L3–L1 (Recommended)
unbalance%Voltage Unbalance at Rated Load (V₂/V₁)
maxWindingCurrent%Highest Winding Current, % of Rated
usablePowerkWUsable Output, Estimate
capacitorRatingVCapacitor Voltage Rating, at Least
voltageL2L3VVoltage L2–L3
voltageL3L1VVoltage L3–L1
usableOutput%Usable Output, % of Rating
supplyCurrentASupply Current
supplyPowerFactornoneSupply Power Factor
capacitorVoltageIdleVRun-Capacitor Voltage, Unloaded
unbalanceIdle%Voltage Unbalance, Unloaded
startTorqueRunOnly%Starting Torque, Run Capacitor Alone
startCapacitorµFStart Capacitor to Add (L3–L1)
capacitorVoltageStartVCapacitor Voltage at Standstill
maxStartTorque%Highest Starting Torque Without Over-Voltage
maxTorqueCapacitanceµFTotal L3–L1 Capacitance for It
secondCapacitorµFBalancer Capacitor L3–L2
inductormHBalancer Inductor L3–L2