Steinmetz Connection Calculator — Run a Three-Phase Motor on Single Phase
Slug steinmetz-connection. Size the run and start capacitors for a three-phase induction motor on a single-phase supply (the Steinmetz connection, or static phase converter), and see what the motor does with them: the three voltages, how unbalanced they are, the most loaded winding's current, the usable output and the voltage each capacitor must be rated for. A second mode gives the capacitor and inductor that balance the motor exactly.
Inputs
Send every one of these in inputs, in the units shown. Most are required: a call without one is refused (400) and costs nothing; one the calculator can do without takes the default shown. An input outside its range is still computed and flagged in the provenance.
| Name | Unit | Range | Default | Description |
|---|---|---|---|---|
| supplyVoltagenumber | V | at least 1 | 230 | The single-phase supply, which must equal the motor's rated line voltage in the connection used: a 230/400 V motor in delta on 230 V, a 208–230/460 V motor in its low-voltage connection on 240 V. |
| frequencynumber | Hz | at least 1 | 50 | Supply Frequency |
| ratedCurrentnumber | A | at least 0.001 | 8.3 | The nameplate current for the connection used (the delta current of a 230/400 V motor on 230 V). |
| powerFactornumber | none | 0.01 … 1 | 0.81 | The nameplate cos φ at rated load. |
| ratedPowernumber | kW | at least 0.001 | 2.2 | The nameplate shaft power; it scales the usable-output estimate. |
| lockedRotorRationumber | × | at least 1.01 | 6 | Starting current as a multiple of rated, from the catalogue or the nameplate code letter; 5 to 7 is typical. |
| lockedRotorPFnumber | none | 0.01 … 1 | 0.4 | Power factor at standstill; 0.3 to 0.5 is typical of small cage motors. |
| noLoadCurrentnumber | % | 1 … 99 | 40 | Current running unloaded, as a percentage of rated; 30 to 60 % is typical of small motors. |
| noLoadPFnumber | none | 0.01 … 1 | 0.1 | Power factor running unloaded; 0.05 to 0.2 is typical. |
| modenumber | none | 0 … 1 | 0 | A run capacitor alone, or the exact balancer: a capacitor on L3–L1 and an inductor (or second capacitor) on L3–L2. |
| runCapacitornumber | µF | at least 0 | 0 | The run capacitor you have, to see what it does; 0 uses the recommended one. Run-capacitor mode only. |
| startTorqueTargetnumber | % | at least 1 | 50 | Starting torque wanted, as a percentage of the motor's three-phase locked-rotor torque. |
Outputs
Returned in values, by key. A value that is unbounded or undefined is null.
| Field | Unit | Description |
|---|---|---|
| runCapacitorheadline | µF | Run Capacitor L3–L1 (Recommended) |
| unbalance | % | Voltage Unbalance at Rated Load (V₂/V₁) |
| maxWindingCurrent | % | Highest Winding Current, % of Rated |
| usablePower | kW | Usable Output, Estimate |
| capacitorRating | V | Capacitor Voltage Rating, at Least |
| voltageL2L3 | V | Voltage L2–L3 |
| voltageL3L1 | V | Voltage L3–L1 |
| usableOutput | % | Usable Output, % of Rating |
| supplyCurrent | A | Supply Current |
| supplyPowerFactor | none | Supply Power Factor |
| capacitorVoltageIdle | V | Run-Capacitor Voltage, Unloaded |
| unbalanceIdle | % | Voltage Unbalance, Unloaded |
| startTorqueRunOnly | % | Starting Torque, Run Capacitor Alone |
| startCapacitor | µF | Start Capacitor to Add (L3–L1) |
| capacitorVoltageStart | V | Capacitor Voltage at Standstill |
| maxStartTorque | % | Highest Starting Torque Without Over-Voltage |
| maxTorqueCapacitance | µF | Total L3–L1 Capacitance for It |
| secondCapacitor | µF | Balancer Capacitor L3–L2 |
| inductor | mH | Balancer Inductor L3–L2 |