Steinmetz Connection Calculator — Run a Three-Phase Motor on Single Phase
Size the run and start capacitors for a three-phase induction motor on a single-phase supply (the Steinmetz connection, or static phase converter), and see what the motor does with them: the three voltages, how unbalanced they are, the most loaded winding's current, the usable output and the voltage each capacitor must be rated for. A second mode gives the capacitor and inductor that balance the motor exactly.
Hogan, Analysis of Single-Phase-to-3-Phase Static Phase Converters, AIEE Paper 55-247 (1956), University of Missouri Engineering Reprint No. 25, eqs. (26), (32) and (33); Pană, Active Load Balancing in a Three-Phase Network by Reactive Power Compensation, ch. 11 in Power Quality – Monitoring, Analysis and Enhancement, InTech (2011), §2 and §4.1API slug steinmetz-connection
Results
LiveRun Capacitor L3–L1 (Recommended) 114.9 µF
- Voltage Unbalance at Rated Load (V₂/V₁)VUF
- 7.6%FAIL
- Highest Winding Current, % of RatedImax
- 146.9%FAIL
- Usable Output, EstimateP
- 1.497kW
- Capacitor Voltage Rating, at LeastVC,min
- 282.5V
At rated load
- Voltage L2–L3V23
- 249.2V
- Voltage L3–L1V31
- 219.1V
- Usable Output, % of RatingP/PN
- 68.1%
- Supply CurrentIs
- 12.19A
- Supply Power Factorcosφs
- 0.9919
Motor unloaded
- Run-Capacitor Voltage, UnloadedV31,0
- 282.5V
- Voltage Unbalance, UnloadedVUF0
- 12.0%FAIL
Starting
- Starting Torque, Run Capacitor AloneTst,run
- 4.4%
- Start Capacitor to Add (L3–L1)Cst
- 350.5µF
- Capacitor Voltage at StandstillV31,st
- 221.3V
- Highest Starting Torque Without Over-VoltageTst,max
- 96.6%
- Total L3–L1 Capacitance for ItCmax
- 609µF
Balancer
- Balancer Capacitor L3–L2C32
- —µF
- Balancer Inductor L3–L2L32
- —mH
- A capacitor alone cannot balance this motor at rated load: load it no further than the usable output shown, or use the balancer mode, a rotary converter or a VFD.
Voltage Unbalance at Rated Load (V₂/V₁) against Rated Power Factor
Drag the operating point or type a value.
Formula
Hogan, Analysis of Single-Phase-to-3-Phase Static Phase Converters, AIEE Paper 55-247 (1956), University of Missouri Engineering Reprint No. 25, eqs. (26), (32) and (33); Pană, Active Load Balancing in a Three-Phase Network by Reactive Power Compensation, ch. 11 in Power Quality – Monitoring, Analysis and Enhancement, InTech (2011), §2 and §4.1
| Symbol | Quantity | Your value |
|---|---|---|
| Crun | Run capacitor between L3 and L1 (µF) | 114.9 µF |
| IN, V, f | Rated current, supply voltage and frequency (A, V, Hz) | — |
| P, Q | The motor's real and reactive power at rated load (W, var) | — |
| Q31, Q32 | Balancer reactive power on L3–L1 (capacitor) and L3–L2 (inductor when positive) (var) | — |
| V1, V_2 | Positive- and negative-sequence voltages at the motor (V) | — |
Assumptions
4 items
- 01The single-phase supply is stiff, and the capacitors and inductor are lossless.
- 02The motor's positive-sequence impedance comes from its nameplate current and power factor at rated load, and from its no-load figures at idle; its negative-sequence impedance is the locked-rotor impedance.
- 03The magnetic circuit is linear: a real motor saturates, so its unloaded voltages are lower than these and the capacitor rating errs on the safe side.
- 04The usable output assumes the winding currents scale with the load; confirm it by measuring them.
Worked example
A lathe motor on a single-phase workshop supply
A lathe has a 2.2 kW three-phase motor, wound for 230 V in delta, drawing 8.3 A at a power factor of 0.81 at rated load. The workshop has a 230 V, 50 Hz single-phase supply. What run capacitor does it need, what does the motor do with it, and what start capacitor gives 50 % of its locked-rotor torque?
| Step | Expression | Result |
|---|---|---|
| Run capacitor, carrying the rated current | 8.3 A / (2π × 50 Hz × 230 V) | 114.9 µF |
| Voltage L2–L3 at rated load | |V₃| | 249.2 V |
| Voltage L3–L1 at rated load | |V₃ − V| | 219.1 V |
| Voltage unbalance at rated load | |V₂| / |V₁| | 7.6 % |
| Most loaded winding, as a share of rated current | max(|I₁ + I₂|, |α²I₁ + αI₂|, |αI₁ + α²I₂|) / 8.3 A | 146.9 % |
| Usable output, estimate | 2.2 kW × 100 / 146.9 | 1.497 kW |
| Run-capacitor voltage with the motor unloaded | |V₃ − V|, Z₁ = Z₀ | 282.5 V |
| Start capacitor to add for the target torque | min C_st : (|V₁|² − |V₂|²) / (V/√3)² ≥ 50 % | 350.5 µF |
| Minimum capacitor voltage rating | max(219.1 V, 282.5 V, 221.3 V) | 282.5 V |
How it works
A three-phase induction motor needs three voltages of equal size, 120° apart. A single-phase supply gives one. The Steinmetz connection, sold ready-made as a static phase converter, feeds the supply to two motor terminals, L1 and L2, and makes the third, L3, with a capacitor from L1. The capacitor's current leads the supply voltage, so the voltage at L3 lands somewhere between the two supply lines and the motor sees a rotating field it can run on.
What the motor sees. Any three voltages split into a forward set that drives the motor and a backward set that brakes it (Fortescue's symmetrical components). The voltage unbalance is the backward set over the forward set, . A motor is built to run with at most 1 % of it long term (IEC 60034-1, clause 7.2.1.1); above 5 % NEMA MG 1 does not recommend running at all. The backward set meets the motor's locked-rotor impedance, which is several times smaller than its running impedance, so a few percent of backward voltage drives a large backward current into the windings, and that current heats them without producing torque. Why one capacitor balances only one load. With the motor running, the current it draws through L3 lags its voltage by the motor's power-factor angle. One capacitor can cancel the backward set only when that angle is 60°, a power factor of 0.5, and then only with the capacitor that carries the motor's rated current at the supply voltage, (Hogan, AIEE 1956). A motor at rated load runs nearer 0.8, so the voltages stay unbalanced, and one winding carries far more than its share. That is where the folk rule that a Steinmetz motor gives about two thirds of its power comes from: the calculator estimates the usable output as the rated current over the highest winding current. The balancer. A capacitor across L3–L1 and an inductor across L3–L2 balance the motor exactly at one load, with reactive powers and for the motor's P and Q. At a power factor of 1 both are , the classic Steinmetz circuit for a resistive load (Pană, InTech 2011); at 0.5 the inductor vanishes and the run capacitor alone remains. This is what an LC network on the motor terminals amounts to: at one frequency any mix of capacitors and inductors between two terminals acts as a single capacitor or a single inductor, and the balancer mode gives that net value for each pair. A series LC tuned to the supply frequency has no impedance at that frequency, so it would short L3 to the supply line and must not be used there. Starting. At standstill the motor's running impedance falls to its locked-rotor impedance, and the run capacitor is far too small to make a rotating field. With no capacitor the field only pulsates and the motor cannot start at all. A start capacitor in parallel with the run capacitor, switched out by a relay or centrifugal switch once the motor is up to speed, gives the starting torque you choose; the calculator finds the least capacitance that reaches it. Light load. Unloaded, the motor draws mostly magnetising current, the capacitor over-compensates it, and the voltage on L3 rises above the supply. The run capacitor must be rated for that voltage, not for the supply's.Practical tips
- Measure the three line voltages and the three winding currents with the motor loaded as it will be in use, and trim the run capacitor until the highest winding current is lowest; the calculator's value is the starting point.
- Fit a bleed resistor across every start capacitor, and discharge the capacitors before touching the terminals: they hold their charge after the supply is off.
- To reverse the motor, swap the supply lines L1 and L2 (or move the capacitors to the other supply line); the values do not change.
- If the motor must deliver its full rating, a single-phase-input VFD is usually the better answer: it makes a balanced three-phase supply and soft-starts the motor too.
- Machines that start under load, such as compressors, need a large start capacitor; check that the target starting torque is reachable before buying parts.
- The results mark the voltage unbalance good up to 1 %, the long-term limit a motor is rated for (IEC 60034-1, clause 7.2.1.1), and out above 5 %, where NEMA MG 1 does not recommend running; the highest winding current is a warning above 100 % of rated and out above 115 %, the service factor many general-purpose motors carry.
Common mistakes
- Using an electrolytic motor-start capacitor as the run capacitor. Start capacitors are built for a few seconds of use; left in circuit they overheat and fail. The run capacitor must be a continuously rated motor-run (film) capacitor.
- Leaving the start capacitor connected. Once the motor is up to speed it drives the L3 voltage and the winding currents far too high; it needs a relay or centrifugal switch to take it out within seconds.
- Rating the run capacitor for the supply voltage. The voltage across it rises when the motor runs unloaded; rate it at least for the highest voltage the calculator shows.
- Connecting a 230/400 V motor in star on a 230 V supply. The supply must equal the motor's rated line voltage in the connection used, which for that motor on 230 V is delta.
- Running the motor at its full nameplate load. With a capacitor alone the windings are unbalanced at rated load and one of them overheats; derate the load, or use the balancer, a rotary converter or a VFD.
Frequently asked questions
5 questions
How big a run capacitor does a three-phase motor need on single phase?
The capacitor that carries the motor's rated current at the supply voltage, , using the nameplate current for the connection you use. It balances the motor exactly only at a power factor of 0.5; at rated load the calculator shows how unbalanced the voltages are and how hard the worst winding works.
Why does a motor on a Steinmetz connection lose power?
A single capacitor cannot balance a motor at its rated-load power factor, so one winding carries more than its rated current. Keeping that winding within its rating means reducing the load; the calculator estimates the usable output as the rated current over the highest winding current.
What does the start capacitor do, and how big should it be?
At standstill the run capacitor alone gives very little starting torque. A start capacitor in parallel with it during start raises the torque; the calculator gives the least capacitance that reaches the starting torque you choose, and the highest starting torque reachable before the motor's forward voltage exceeds its rating.
Can an inductor and a capacitor balance the motor exactly?
Yes, at one load: a capacitor on L3–L1 and an inductor on L3–L2, sized by and . Away from that load the balance drifts again. Below a power factor of 0.5 the second part becomes a capacitor.
What voltage rating does the run capacitor need?
At least the highest voltage it sees, which is usually with the motor unloaded, when the capacitor over-compensates the magnetising current and the generated phase rises above the supply. The calculator reports that voltage as the minimum rating.
References
Analysis of Single-Phase-to-3-Phase Static Phase Converters · Active Load Balancing in a Three-Phase Network by Reactive Power Compensation · IEC 60034-1:2010 Rotating electrical machines — Part 1: Rating and performance
- Analysis of Single-Phase-to-3-Phase Static Phase Converters — J. C. Hogan, AIEE Paper 55-247 (1956), University of Missouri Engineering Reprint No. 25 — eq. (26): balance is zero negative-sequence current; eqs. (32)–(33): a capacitor alone balances only a motor at a power factor of 0.5
- Active Load Balancing in a Three-Phase Network by Reactive Power Compensation — A. Pană, ch. 11 in Power Quality – Monitoring, Analysis and Enhancement, InTech (2011) — §2: the Steinmetz circuit, susceptances ±G/√3; §4.1, eqs. (41)–(45): the general balancing susceptances
- IEC 60034-1:2010 Rotating electrical machines — Part 1: Rating and performance — Clause 7.2.1.1: three-phase motors are suitable for a negative-sequence voltage of at most 1 % of the positive sequence over a long period, or 1.5 % for a few minutes