Rotary Phase Converter Calculator — Idler and Balancing Capacitors
Size the balancing capacitors of a rotary phase converter: the idler motor generates the third leg from a single-phase supply, and capacitors from that leg to each supply line even out the three voltages. See the set that balances the idler alone, the set for the load motor at full load, the capacitance to switch in between them, and what each set does at the other load, with the idler's winding current and its start capacitor.
Pană, Active Load Balancing in a Three-Phase Network by Reactive Power Compensation, ch. 11 in Power Quality – Monitoring, Analysis and Enhancement, InTech (2011), §4.1, eqs. (41)–(45); Hogan, Analysis of Single-Phase-to-3-Phase Static Phase Converters, AIEE Paper 55-247 (1956), University of Missouri Engineering Reprint No. 25, eq. (26)API slug rotary-phase-converter
Results
LiveIdle Set: Capacitor L3–L1 44.1 µF
- Full-Load Set: Capacitor L3–L1C31,F
- 176µF
- Capacitance to Switch In (L3–L1)ΔC31
- 131.9µF
- Idle Set Under Full Load: UnbalanceVUF
- 6.6%FAIL
- Idle Set Under Full Load: Load-Motor Winding, % of RatedIL,max
- 118.1%FAIL
Idle set (idler alone)
- Capacitor L3–L2C32,0
- 31.03µF
- Inductor L3–L2L32,0
- —mH
Full-load set
- Capacitor L3–L2C32,F
- —µF
- Inductor L3–L2L32,F
- 438.1mH
- Unbalance at Full Load, Capacitors OnlyVUF
- 1.4%CHECK
- Load-Motor Winding at Full Load, Capacitors Only, % of RatedIL,max
- 107.8%CHECK
No capacitors
- Voltage L2–L3V23
- 208.6V
- Voltage L3–L1V31
- 215.6V
- Voltage Unbalance (V₂/V₁)VUF
- 5.8%FAIL
Idle set under full load
- Voltage L2–L3V23
- 217.8V
- Voltage L3–L1V31
- 205.3V
- Idler Winding, % of RatedIi,max
- 69.8%PASS
Full-load capacitors at idle
- Voltage L2–L3V23
- 270.6V
- Voltage L3–L1V31
- 280.5V
- Voltage UnbalanceVUF
- 11.6%FAIL
- Idler Winding, % of RatedIi,max
- 114.9%CHECK
Idler start
- Start Capacitor to Add (L3–L1)Cst
- 511.7µF
- Capacitor Voltage at StandstillV31,st
- 179.7V
- Highest Starting Torque Without Over-VoltageTst,max
- 97.6%
- An idler winding carries more than its rated current in at least one state shown: see the idler current results, and use a larger idler or switch the capacitors with the load.
- A load-motor winding carries more than its rated current under full load with the capacitors shown: see the load-motor current results, and switch in the full-load capacitance or use a larger idler.
Idle Set Under Full Load: Unbalance against Idler Rated Current
Drag the operating point or type a value.
Formula
Pană, Active Load Balancing in a Three-Phase Network by Reactive Power Compensation, ch. 11 in Power Quality – Monitoring, Analysis and Enhancement, InTech (2011), §4.1, eqs. (41)–(45); Hogan, Analysis of Single-Phase-to-3-Phase Static Phase Converters, AIEE Paper 55-247 (1956), University of Missouri Engineering Reprint No. 25, eq. (26)
| Symbol | Quantity | Your value |
|---|---|---|
| Y1 | Positive-sequence admittance: the idler alone (idle set), or the idler and the load motor (full-load set) (S) | — |
| B31, B32 | Balancing susceptance L3–L1 and L3–L2: a capacitor when positive, an inductor when negative (S) | — |
| C | Capacitance of a positive susceptance (µF) | — |
| V, f | Supply voltage and frequency (V, Hz) | — |
Assumptions
4 items
- 01The single-phase supply is stiff, and the capacitors are lossless.
- 02The idler motor runs at its no-load point and the load motor at its rated load; each motor's negative-sequence impedance is its locked-rotor impedance, with one locked-rotor ratio and power factor for both.
- 03The magnetic circuits are linear: a real idler motor saturates, so a generated phase shown above the supply is lower in practice.
- 04Where the full-load set calls for an inductor on L3–L2, the full-load capacitors are evaluated without it, at idle and at full load.
Worked example
A converter for a lathe
A workshop builds a rotary converter on a 230 V, 50 Hz single-phase supply, with an idler motor drawing 13.5 A at rated load and 35 % of that running unloaded, at a power factor of 0.1. It runs a lathe motor drawing 8.3 A at a power factor of 0.81. Which capacitors balance it idling, which at full load, and what does each set do at the other load?
| Step | Expression | Result |
|---|---|---|
| Idle set, capacitor L3–L1 | (Re Y₁/√3 − Im Y₁/3) / (2π × 50 Hz), Y₁ = 1/Z₀ | 44.1 µF |
| Idle set, capacitor L3–L2 | (−Re Y₁/√3 − Im Y₁/3) / (2π × 50 Hz), Y₁ = 1/Z₀ | 31.03 µF |
| Full-load set, capacitor L3–L1 | (Re Y₁/√3 − Im Y₁/3) / (2π × 50 Hz), Y₁ = 1/Z₀ + 1/Z_L | 176 µF |
| Full-load set, L3–L2 becomes an inductor | 1 / (2π × 50 Hz × |B₃₂|) | 438.1 mH |
| Capacitance to switch in on L3–L1 with the lathe | 176 µF − 44.1 µF | 131.9 µF |
| Idle set under full load: voltage unbalance | |V₂| / |V₁| | 6.6 % |
| Full-load capacitors at idle: voltage L3–L1 | |V₃ − V| | 280.5 V |
| Full-load capacitors at idle: the idler motor's most loaded winding | max(|I_a|, |I_b|, |I_c|) / 13.5 A | 114.9 % |
How it works
A rotary phase converter makes the third phase with a spinning machine instead of a capacitor alone. An idler motor, an ordinary three-phase induction motor with nothing on its shaft, is started on the single-phase supply across L1 and L2. Once it turns, its rotor carries the rotating field round, and its third winding generates a voltage on L3. The machine it runs, the load motor, connects to L1, L2 and L3 like any three-phase supply.
Why the generated phase sags. The idler motor's third winding has impedance, so the voltage on L3 falls as current is drawn from it, and the three voltages are unbalanced even with the idler motor running alone. The backward-rotating part of that unbalance meets each motor's locked-rotor impedance, which is small, so it drives large currents. The idler motor's low backward impedance is in fact what makes the converter work: it soaks up much of the unbalance that would otherwise reach the load motor. Balancing capacitors. Capacitors from L3 to the supply lines restore the balance. With the three voltages equal, the backward set is zero, so the motors' backward impedances drop out, and the balancing parts follow from the forward-sequence admittance alone. They are the Steinmetz balancer in its general form: a susceptance of on L3–L1 and on L3–L2 (Pană, InTech 2011), a capacitor where it is positive and an inductor where it is negative. The idler motor running alone draws mostly magnetising current, so its set is two capacitors. Adding the load motor adds real power, which pushes the L3–L1 capacitor up and the L3–L2 part toward an inductor. One set cannot suit both loads. Because the balancer is linear in the admittances, the capacitance to add when the load motor runs is exactly that motor's own Steinmetz balancer. Capacitors set for the idler motor alone leave the voltages sagging and unbalanced under full load; capacitors set for full load push the generated phase well above the supply when the load motor stops, and can overload the idler motor. Converter builders split the difference, or switch extra capacitance in with the load motor's contactor. The calculator shows both sets, their difference, and what each does at the other load. Starting the idler motor. An idler motor on single phase cannot start by itself. A start capacitor across L3–L1, switched out once it is up to speed, gives it the starting torque you choose; an unloaded idler motor needs little. Sizing the idler motor. A larger idler motor has a lower backward impedance relative to the load, so it holds the generated phase up better under load. The chart sweeps the idler motor's size and shows the unbalance of the idle set under full load.Practical tips
- Measure the three line voltages with the converter idling and again with the load motor working, and trim the capacitors so the generated phase sits close to the supply at the load you use most.
- Switch the extra capacitance for full load with the load motor's contactor, so the converter is balanced at both idle and full load.
- Fit bleed resistors across all the capacitors, and discharge them before working on the converter.
- Start the idler motor before the load motor, and keep the load motor's starting current in mind: it draws several times its rating through the idler motor during start.
- For one machine that needs speed control or a soft start, a single-phase-input VFD may replace the converter altogether.
- To reverse the load motor, swap two of its leads, preferably L1 and L2 so the generated phase stays on its own terminal; exchanging the supply lines L1 and L2 at the converter (or moving the capacitors to the other supply line) reverses everything it runs, and none of the values change.
- The results mark the voltage unbalance good up to 1 %, the long-term limit a motor is rated for (IEC 60034-1, clause 7.2.1.1), and out above 5 %, where NEMA MG 1 does not recommend running; the highest winding current is a warning above 100 % of rated and out above 115 %, the service factor many general-purpose motors carry.
Common mistakes
- Balancing the converter with the idler motor alone and expecting the same voltages under load. The generated phase sags as the load motor draws current; check the idle set's unbalance under full load.
- Leaving the full-load capacitors in with the load motor off. The generated phase rises well above the supply and the idler motor's windings can overheat; switch the extra capacitance with the load.
- Using an idler motor smaller than the load motor. The smaller the idler motor, the less of the unbalance it absorbs; watch the idler motor current and the unbalance under load.
- Wiring single-phase loads, such as control transformers or coolant pumps, to the generated phase. Connect them across L1 and L2, the true supply.
- Rating the capacitors for the supply voltage. The generated phase can rise above it at light load; rate them for the highest voltage shown.
Frequently asked questions
5 questions
How do I size the capacitors for a rotary phase converter?
From the idler motor's no-load current and power factor for the set that balances it idling, and from both motors together for the set that balances it at full load. The calculator gives both, as a capacitor (or inductor) on L3–L1 and on L3–L2, and the difference between them.
Why is the generated phase voltage low under load?
The idler motor's third winding has impedance, so the voltage it generates falls as current is drawn from it. Capacitors from the generated phase to the supply lines raise it; the calculator shows the voltages with no capacitors, with the idle set under load and with the full-load set at idle.
How big should the idler motor be?
Larger than the load motor is the usual practice: a larger idler motor holds the generated phase up better. The calculator shows the unbalance and the idler motor's winding current under load for the idler motor you enter, and the chart sweeps the idler motor's size.
Can the same capacitors work at idle and at full load?
Not exactly. The set that balances the idler motor alone leaves the voltages unbalanced under load, and the full-load set over-compensates at idle. Switching the difference in with the load motor balances both.
Why does the full-load set need an inductor on one side?
Real power drawn by the load motor needs a capacitor on one pair and an inductor on the other to balance exactly. Converters are built with capacitors only, so that side is left without a part at full load, and the calculator shows the unbalance that leaves.
References
Active Load Balancing in a Three-Phase Network by Reactive Power Compensation · Analysis of Single-Phase-to-3-Phase Static Phase Converters · IEC 60034-1:2010 Rotating electrical machines — Part 1: Rating and performance
- Active Load Balancing in a Three-Phase Network by Reactive Power Compensation — A. Pană, ch. 11 in Power Quality – Monitoring, Analysis and Enhancement, InTech (2011) — §2: the Steinmetz circuit; §4.1, eqs. (41)–(45): the general balancing susceptances, linear in the load admittances
- Analysis of Single-Phase-to-3-Phase Static Phase Converters — J. C. Hogan, AIEE Paper 55-247 (1956), University of Missouri Engineering Reprint No. 25 — eq. (26): balance is zero negative-sequence current; eqs. (32)–(33): a capacitor alone balances only a power factor of 0.5
- IEC 60034-1:2010 Rotating electrical machines — Part 1: Rating and performance — Clause 7.2.1.1: a negative-sequence voltage of at most 1 % of the positive sequence over a long period, or 1.5 % for a few minutes
Reduces to Hogan's single-capacitor balance when the motors run at a power factor of 0.5, and to Pană's resistive balancer for a load at a power factor of 1; the engine agrees with an independent solve of the same circuit to 1e-9.